Autec Remote Display Weight

LIAMIE00-03

To zero out weight on display, open receiver box in control panel.  Switch rotary dial to 1.  This should change display screen to set Dta.  Dta is the minimum limit.  Set to 0 with no load on the hook.  Small buttons on receiver near rotary switch are + and -.  Once it’s zero and, hold both buttons until the remote display says “result: success”.  Dtb is the maximum limit and both need calibrated to be accurate on display.  Dtb needs to be 50% of maximum load.

Liebherr Login Code

When logging into the diagnostic menu, code is (month + date) + (hour + minutes)  example if it is 4/15 at 14:30…its (19) + (44) = 63  code will be 63 for one minute.  Hit the “+” 63 times to get to correct code

Potain MA13 Drive Error Short Circuit and no read out on Hoist Drive

Went to set up crane

Smoke coming out of hoist drive and trolley drive getting short circuit code

Unhooked output side of hoist and still tripping breaker.  Bad Drive

Unhooked output side of trolley drive still getting error bad drive

Replacement drives Part Numbers

Trolley (New updated drive only) 8201-1312 Kit to upgrade from Altavar 58 8200-7514

Swing W-81406-89 Kit 8200-0671

Hoist A-81406-46 Kit 8200-7510

Transformer wiring

Internally, H1 to Black on output cord and H10 to White on output cord. Green to ground and red goes to nothing.

Externally on output cord end, red is X, black is Y, white is W and green to ground