Trolley drive faults when you trolley in or out
Drive starts up as normal, but when you try to trolley in or out, F0503 fault appears.
Bonfiglioli F0503 is an error code indicating a DC-Link Overcurrent fault
Found input power connector on the bottom of the drive was loose. Pushed it back in completely, and crane is working well.
Maintenance mode
Bringing the crane down in maintenance mode for checking the trolley or replacing hoist rope. It is not in the manual to do this. You need to push the escape and the down arrow on the LOGO to bypass all sensors then you will need to jumper the banana bar in the back.n This is jumpering the banana bar moment for trolley and hoist. You also need to either loosen the banana bar senors or unbolt them as it will crush them with the jib tip to the ground. That would also mean they need recalibrated.
From the picture it looks like we are jumpering 26T1 to NC-SLL and NC-SP to 26T1 and removing the blue and white wire out of NC-SLL

How to move trolley in mounting
When in mounting to move trolley you need to push the auxiliary button on the side of the remote wait for the Hydraulic pump to stop and then you have functions of trolley in. In order to get trolley out you have to by pass all the sensors on the LOGO by holding down the down arrow button and the esc button.



FM Gru Electrical Schematics
When look at a component in the electrical cabinet or wire, the number indicates what page in the schematics that the component can be found at. For example, 6U1 is the hoist inverter (VFD) found on page 6. Wire #1503 is found on page 15 and is wire# 03 in a sequence.
S=Hoist (pg 6)
R=Slew (swing) (pg 9)
C=Trolley (pg 12)
KL= Safety validation for the drives
FM Gru will not start

Crane will not start with remote control and display shows “Remove Inserted Commands”
A joystick is out of adjustment and not returning to neutral. Can try and clean connections on the back of joystick, or use app to recalibrate remote.
FM Gru won’t start
When trying to start crane, the PLC and the load sensor were not turning on. The top light on this device was flashing red.

This is an electronic circuit break. Found the short, and corrected. The red light can be pushed to reset.


F=Brake