Potain MA13 Drive Error Short Circuit and no read out on Hoist Drive

Went to set up crane

Smoke coming out of hoist drive and trolley drive getting short circuit code

Unhooked output side of hoist and still tripping breaker.  Bad Drive

Unhooked output side of trolley drive still getting error bad drive

Replacement drives Part Numbers

Trolley (New updated drive only) 8201-1312 Kit to upgrade from Altavar 58 8200-7514

Swing W-81406-89 Kit 8200-0671

Hoist A-81406-46 Kit 8200-7510

Transformer wiring

Internally, H1 to Black on output cord and H10 to White on output cord. Green to ground and red goes to nothing.

Externally on output cord end, red is X, black is Y, white is W and green to ground

Honking Horn during known weight on scaling

Scaled crane and went to do known load and horn just started honking.

Had 4 tower sections in and 45 degree avoidance on in the scaling process.  You can’t have 45 degree avoidance on with 4 tower section in unless you have central ballast.

Went back in and put x through 45 degree avoidance and it worked fine and was able to finish scaling