HUP 40/30 with Dasoon and smaller gen sets UPDATED 1/17/19

Dustin,

Yes, the Fault can be changed in screen 31.21 to No Action. We can try this and see if that eliminates the issue. The suggestion from ABB is to download the ABB diagnostic software and map the DC voltage from the drive to the motor during this Fault condition time. Also, my contact suggested calling the ABB tech support line (1 800 4357 365) and start a case. The technician from ABB may have prior experience with this issue and provide more guidance. You will need the drive model and serial number for the call.

Chuck Burton
Product Trainer/Technical Services
Doosan Portable Power

1293 Glenway Drive
Statesville, NC 28625
T 704.883.3669
M 336.469.4835
chuck.burton@doosan.com
www.doosanportablepower.com

 

8528 is pass to get into drive under folder 96

Update as of 1/17/2019 – Turning off 31.21 (0) allows both the Wacker G25 and Doosan generators to erect Hups without fail (3130 code on slew drive).  The status of 31.21 will automatically revert to (1) or active.

On slew drive press <ENTER>  and down arrow until the Gear Cog (settings) shows.  Press <ENTER> at the file folder icon and scroll to 96 and press <ENTER>.  Scroll to 96.02 and enter code above.  Press <EXIT> to get to 31 and press <ENTER> and <ENTER> again at 31.21.  Change to <0>

 