Hoist Motor Not Working in Very Cold Temperatures

TA20-236-A – Operating mode for TUN function ATV320 on HUP cranes_EN (2)

 

Suggestion per France

Here is a procedure for making a motor tune on the ATV320 hoisting motor drive.

In green : menu and parameters of the drive HMI.

For this operation, the crane must be in « work » configuration.

Unlock the hoisting drive :

Mod (Non) / Cod- / Cod / enter : 2024

(press esc, esc, esc to go back to the main menu)

Change command channel from CANopen to terminal (needed for manual tune ) :

Conf / Full / Ctl- / Fr1 / change Can for AI1 (looks like A11) Must Scroll to the left 

Make the motor tune :

Conf / full / Drc- / ASY- / Tune change No for YES then press enter for 5 seconds to launch the tune.

Check that the tune is done

Conf / full / Drc- / ASY- / TUS this parameter displays Done if the tune is well done.

If possible note the new value of RSA parameter  (unable to do)

Conf / full / Drc- / ASY- / rSA read and note the value.

Re-change the command channel from terminal to CANopen

Conf / Full / Ctl- / Fr1 / change AI1 for Can

Hiab moving EXTREMELY slow swinging

Under the display on remote press left button for code reading.

Called Hiab and codes indicated that slew sensor was not communicating to processor.  Removed face of crane  (where e-stop is located) and found 2 wires pulled out.  Replaced connectors and reinstalled.

T85 keeps shutting off

Fault is 1-230-026, slew encoder failure.  Instead of changing to “disconnected” in the slew drive, changed to “Partially Open Loop”.  Allowed crane to continue operation.

Menu to change parameters in Slew Drive

Menu

Parameters

Complete list

96 System Menu

02 Pass code

Last two are 71

Back

Menu 74

Menu 12

Partially Open Loop