Code 7510
Had customer check power
L1-L2 290V L2-L3 290V L1-L3 290V
Hoist and trolley would work. Turn up power on generator to 476V. All is good at this time.
Code 7510
Had customer check power
L1-L2 290V L2-L3 290V L1-L3 290V
Hoist and trolley would work. Turn up power on generator to 476V. All is good at this time.
On the rear of the mount for the dynametric ring located at the rear of the crane, is an adjustment bolt. On the side of the mount, there is an access plate to reach the bolt head. Remove plate, and adjust screw. Clockwise will allow load to mover further out on the jib, Counter-Clockwise will cutout movement sooner.
TA20-236-A – Operating mode for TUN function ATV320 on HUP cranes_EN (2)
Suggestion per France
Here is a procedure for making a motor tune on the ATV320 hoisting motor drive.
In green : menu and parameters of the drive HMI.
For this operation, the crane must be in « work » configuration.
Unlock the hoisting drive :
Mod (Non) / Cod- / Cod / enter : 2024
(press esc, esc, esc to go back to the main menu)
Change command channel from CANopen to terminal (needed for manual tune ) :
Conf / Full / Ctl- / Fr1 / change Can for AI1 (looks like A11) Must Scroll to the left
Make the motor tune :
Conf / full / Drc- / ASY- / Tune change No for YES then press enter for 5 seconds to launch the tune.
Check that the tune is done
Conf / full / Drc- / ASY- / TUS this parameter displays Done if the tune is well done.
If possible note the new value of RSA parameter (unable to do)
Conf / full / Drc- / ASY- / rSA read and note the value.
Re-change the command channel from terminal to CANopen
Conf / Full / Ctl- / Fr1 / change AI1 for Can
Under the display on remote press left button for code reading.
Called Hiab and codes indicated that slew sensor was not communicating to processor. Removed face of crane (where e-stop is located) and found 2 wires pulled out. Replaced connectors and reinstalled.
Crane not receiving 24 volts from converter – replace converter
Hiab XS 322 HiPro E-7
Fault is 1-230-026, slew encoder failure. Instead of changing to “disconnected” in the slew drive, changed to “Partially Open Loop”. Allowed crane to continue operation.
Menu to change parameters in Slew Drive
Menu
Parameters
Complete list
96 System Menu
02 Pass code
Last two are 71
Back
Menu 74
Menu 12
Partially Open Loop
Manual shows error at current supply to Slew Drive. Crane was running on a new generator (14 hours) and failed. United Rentals came out and put a load bank on the generator and its working again.
There are 2 antenna connections on the top of the receiver. The red antenna (Gainflex) goes on the right. It is for sending feedback for the display on the remote.